NFPA 70E: The Standard for Electrical Safety in the Workplace

inline switch-rated motor plug
Connection and disconnection of a DECONTACTOR™ Series Plug and Receptacle
is a NFPA 70E defined 'Normal Operation'.
PPE is not required.

As the foremost consensus standard for electrical safety in the workplace, NFPA 70E is the primary resource for employers
to use in determining how to comply with OSHA’s electrical
safety regulations. It is also used by OSHA and the courts in the investigation of injuries in order to assess whether or not the involved employers took reasonable steps and precautions to protect their employees.

The key elements of the standard are summarized below. Complete details should be obtained from the standard itself.







Article 110 – General Requirements for Electrical Safety-Related Work Practices

Training Requirements (110.6)

Employees who may be exposed to electrical hazards must be specifically trained to understand the
hazards associated with electrical energy as well as the safety-related work practices and procedures required to provide protection from them. The level of training provided determines the tasks that an employee is qualified to perform.

Only specially ‘Qualified Persons’ may perform work on or near exposed and energized electrical conductors or circuit parts. The training requirements include:

Electrical Safety Program (110.7)

Employers are required to implement and document an electrical safety program to direct employee activities in a manner that is appropriate for the different voltage, energy level and circuit conditions that may be encountered. This safety program shall include all electrical safety procedures, be documented in writing, and be made available to all employees. If work on or near energized electrical conductors and circuit parts operating at 50V or more is required, the safety program must:

Working While Exposed to Electrical Hazards (110.8)

Safety work practices consistent with the nature and extent of the associated electrical hazards shall be used to safeguard employees from injury while working on or near exposed electrical or circuit parts that are or can become energized. Two primary conditions are identified and addressed:

  1. Energized Electrical Conductors and Circuit Parts – Safe Work Condition. Live parts to
    which an employee might be exposed shall be put into an electrically safe work condition before employees can work on or near them, unless work on energized components can be justified
    according to section 130.1.

  2. Energized Electrical Conductors and Circuit Parts – Unsafe Work Condition. Only qualified persons may work on electrical conductors or circuit parts that have not been put into an electrically safe work condition.

The requirements for establishing an electrically safe work condition are indicated in Article 120, while
the requirements for work involving electrical hazards are covered in Article 130.

Article 120 – Establishing an Electrically Safe Work Condition

The most effective way to prevent an electrical injury is to completely remove the source of electrical
energy and eliminate the possibility of its reappearance. To do so, workers must identify and disconnect
all possible sources of electricity.

Process of Achieving an Electrically Safe Work Condition (120.1)
  1. Identify all possible sources of electric supply.
    Care should be taken to identify the possible presence of secondary sources.

  2. Properly interrupt the load current(s) and open the disconnecting device(s).
    Not all disconnecting devices are rated to interrupt load currents; this should only be done with a properly rated device.

  3. Verify deenergization through visual inspection of the disconnect contacts.
    Disconnecting means may sometimes fail to open all phase conductors when the handle is operated,
    so it is necessary to verify physical contact separation. If this requires removing the disconnect
    door or cover, appropriate PPE must be used.

  4. Apply lockout/tagout devices.
    This should be done in accordance with a formally established company policy.

  5. Use a voltage detector to test each conductor to which the worker may be exposed in
    order to verify deenergization.

    The voltage detecting device must be functionally tested both before and after taking the measurements in order to ensure that it is working satisfactorily.

  6. Circuit parts with induced voltages or stored electrical energy must be grounded.
    If the conductors being deenergized could contact other energized conductors or circuit parts, grounding devices rated for the available fault duty should be applied.
Justification (130.1)

Deciding to work on or near energized electrical conductors and circuit parts should be a last resort in
the workplace, after all other opportunities for establishing an electrically safe work condition have been exhausted. Work on energized parts at 50V or more should only be performed if the employer can demonstrate that deenergizing will introduce additional hazards or is not feasible due to equipment
design or operational limitations.

When non-routine work must be performed on energized parts, a detailed work permit must be
prepared before the work can start. The work permit must document the following elements and be approved by a responsible manager or safety officer:

Approach Boundaries to Energized Electrical Conductors or Circuit Parts (130.2)

Limited and restricted approach boundaries must be determined in order to identify safe approach distances and the precautions required to minimize the possibility of shock.

Arc Flash Risk Assessment (130.3)

An arc flash hazard analysis shall be done in order to protect personnel from the possibility of being
injured by an arc flash. As part of this analysis, flash protection boundaries must be determined based
on available bolted fault currents and the incident energy exposure level for personnel working within
this boundary must be calculated.

Personal and Other Protective Equipment (130.7)

Employees working in areas where electrical hazards are present shall be provided with, and shall use, protective equipment that is designed and constructed for the specific part of the body to be protected
and for the work to be performed.

The NFPA 70E standard provides a table that identifies if Arc Flash PPE is required for a particular task. If PPE is required another table lists arc flash PPE categories and boundaries depending on equipment being worked on. A third table lists PPE requirements for each category.

Selection of PPE using tables
Step 1: Determine if Arc Flash PPE is required:

Table 130.7(C)(15)(A)(a) Arc Flash Hazard Identification (Abridged)

Task Arc Flash PPE Required
Opening hinged door(s) or cover(s) (to expose bare energized electrical conductors and circuit parts)
Yes

Step 2: Determine Arc Flash PPE Category:

Table 130.7(C)(15)(A)(b) Arc Flash Hazard PPE Catagories (Abridged)

Equipment Arc Flash PPE Category Arc Flash Boundary
Panelboards or other equipment rated 1 485 mm (19 in)
Panelboards or other equipment rated >240V and up to 600V 2 900 mm (3 ft)

Step 3: Determine PPE Requirements:

Table 130.7(C)(16)Personal Protective Equipment (PPE) (Abridged)

PPE Category PPE (abridged)
1 Arc-rated (level 4) long sleeve shirt, pants, coverall, jacket, safety glasses, footwear
2 Arc-rated (level 8) long sleeve shirt, pants, coverall, jacket, safety glasses, footwear